Input | Model | MC053V RF |
DC Input Voltage | 198-264V AC 50Hz | |
Rated Voltage | 220V-240VAC 50Hz | |
Stand-by Power | <1W | |
Surge Test | L N:1KV | |
Output | Working Mode | ON/OFF 1-10V/ PUSH dimming |
Type of Load | Inductive or Resistive | |
Load Capacity | 400W (Inductive) 800W (Resistive) |
|
Max. Surge Capacity | 50A (50% Ipeak, twidth =500uS, 230Vac full load, cold start); 80A (50% Ipeak, twidth =200uS, 230Vac, full load, cold start) |
|
1-10v interference | 1-10Vdimming port | 1-10V current:50mA Max |
Cable type | push | |
Sensor Parameters | Operating Frequency | 5.8 GHz ±75 MHz,ISM Band. |
Transmitting power | 0.5mW Max. | |
Hold time | 5S/30S/90S/3min/20min/30min/+∞ | |
Dimming level | 10%/20%/30%/50% | |
Stand-by period | 0S/5S/5min/10min/30min/60min/+∞ | |
Detection area | 100%/75%/50%/25% | |
Daylight sensor | 5lux/15Lux/30Lux/50Lux/100lux/150lux/Disable | |
Detection range | 6-8m (3m mounting height) | |
Mounting height | 8m Max | |
Detection angle | 150° | |
RF module | Frequency | 820MHz-880MHz Center Frequency:868MHz |
Transmission power | -5dBm…+20dBm | |
Transmission distance | Max. 100m in the free field Max. 50m inside buildings |
|
Modulation Mode | FSK | |
Operating | Operating Temperature | -25~+60℃ |
Environment | ||
Storage Temperature | Temperature: -40℃…+80℃; Humidity: 10%-95% (Non-condensing) | |
Certificate Standards | Safety standards | EN61058-1 |
EMC standards | N/A | |
Environmental Requirement | Compliant to RoHS | |
Certificate | CE | |
Others | Wiring | Press-in Type Terminals, wire diameter:0.75-1.5mm2 |
IP Rating | IP20 | |
Protection Class | Class II | |
Installation | Built-in | |
Dimension | 112*50*28.5mm | |
Package | Bubble bag + clapboard +carton(K=A) | |
Lifetime | 5 years warranty@Ta 230V full load | |
Note 1. “N/A” means not available. 2. The detection range of the sensor is related to the moving speed and size of moving object, mounting height, installation height and angle, installation site, reflectors around the sensor etc. The data in the document is typical value and tested?by a 165cm person?in an open indoor area. The detection range at wall mounting will be longer at ceiling mounting. Please reduce detection sensitivity at wall mounting or contact us to confirm the sensor data settings. |
Initialization
The light will turn on 100% brightness in the initial energizing sensor, and turn off after 10 seconds. During initialization, no external motion sensing signal will be detected.
Default settings
Detection Area: 100%, Hold Time: 5S,Stand-by period:0s, Daylight Sensor: Disable,Stand-by DIM level:10%,RF Brightness:10%-50%,RF:Open ,Mode:Broadcast ,TX:A, RX:A
Note:
The detection range at wall mounting will be longer at ceiling mounting. Please reduce detection sensitivity at wall mounting or contact us to confirm the sensor data settings.
*The sensor is designed to connect one load only. Connect more than one load may damage the sensor.