                | Charge Part | KE022- | 01AM180HB1 | 01AM180HB | 
| Rated input voltage | 220-240Vac 50Hz /60Hz | ||
| Rated input current | 0.06A Max. @230Vac | ||
| Input inrush current | 30A(twidth=100uS 50% Ipeak )@230Vac(Cold start at full load ) | ||
| Power factor | ≥0.5@230Vac | ||
| Input power | <3W | ||
| Battery charging current (Max) | 200mA | ||
| Battery charging time | 24 hours Max. | ||
| Emergency Part | Operating mode | Emergency mode | |
| Load type | LED | ||
| Emergency power | 1W | ||
| Emergency time | 3hours | ||
| Load output current | 100-15mA | 20-5mA | |
| Load output voltage | 10-60VDC | 50-180VDC | |
| Battery | LifePO4 (The battery capacity meets the emergency time at 25℃) | 3.2V 1800mAh | |
| Battery warranty | Warranty 5 year. | ||
| Exception Driver Requirements | Surge current | 8A | |
| Input current | 3 A Max. | ||
| Output current | 2A | ||
| LED Indication | Charging | Green light | |
| Fault | Green light off | ||
| Emergency Function Test | Manual test | Default | |
| Auto test | Settable | ||
| Auto Testing | Fault / test / Status | Reason | Charge Indicator Status | 
| Battery fully charged and operational | Standard daily use | solid green | |
| Battery Charging | Initial Charge/Battery Top Up | Flashing green 1 sec on 1 sec off | |
| Auto Test 3 Hours (every 12 months) | Periodic self test | Flashing Green 3 sec on 1 sec off | |
| Auto Test 5 Min (every 30 days) | Periodic self test | Flashing Green 3 sec on 3 sec off | |
| Duration test fault | Failed the 3 hour annual test | Flashing Red 0.5 sec on 0.5 sec off | |
| LED fault | Not plugged in or damaged/faulty | Flashing Red 2 sec on – 2 sec off | |
| Battery Disconnected/Faulty | Not plugged in or damaged/faulty | solid red | |
| Emergency protection | Battery over-charge/deep discharge protection | Yes | |
| Output over-voltage protection | Yes | ||
| Output overload protection | Yes | ||
| Output short circuit protection | Yes | ||
| Operating Environment | Operating temperature/humidity | 0℃…+50℃humidity:20%-75%(without condensation) | |
| Storage temperature/humidity | -5℃-35℃ | ||
| Case Max. Temp(Tc) | 75℃ | ||
| Safety & EMC | Withstand voltage | 3000Vac 5mA 60s (Input “L N” – output “SEC+ SEC-) | |
| Safety standard | EN61347-1, 60598-2-22, 61347-2-7, 62034 | ||
| EMC standard | EN55015, EN61000-3-2, EN61000-3-3 | ||
| Battery standard | UN38.3 | ||
| Environmental protection requirements | Compliant to RoHS | ||
| Certification | CE | ||
| Others | Input/output(terminal/wiring) specification | Press terminal, wire diameter:0.5-0.75mm2 | |
| IP rating | IP20 | ||
| Type of protection | Class 2 | ||
| Installation type | Built-in installation | ||
| Installation dimension | 134*42*22mm | ||
| Packaging requirement | White box+Instruction manual+clapboard+outer carton(K=A) | ||
| Weight :Emergency Power Supply | 150g | ||
| Lifespan | 5 Year @Ta ( Battery not included ) | ||
| Notes:All parameters are tested on the input voltage 230Vac,environment temperature 25℃,unless otherwise specified. | |||
Manual Test & Operation Instructions
Automatic Test& Operation Instructions
Battery Application Notice
 
 
N/A
 
                    