Input | Models | 150mA | 200mA | 250mA | 300mA | 350mA | 700mA | |
Operating Voltage | 198-264VAC 50Hz /60Hz | |||||||
Rated Input Voltage | 220-240VAC 50Hz /60Hz | |||||||
DC Input Voltage range | 200-240VDC | |||||||
Input Cuttent | 0.06A Max. | |||||||
Input Inrush Current | <10A (Half current pulse width 100US) @230VAC | |||||||
Power Factor | ≥0.9C @230VAC (Full load) | |||||||
Total harmonic distortion | Typical: 20% (@230Vac, 100% load) | |||||||
Stand-by Power | ≤0.5W(@230Vac) | |||||||
Efficiency | 83%Max. @230VAC (Full load) | |||||||
Wiring Method | INPUT: AC:0.5mm² DALI:0.5mm²; | |||||||
Automatic circuit breaker (Calculate current in the wire) |
type | B10 | B13 | B16 | B20 | B25 | / | |
Number | 40 | 50 | 65 | 85 | 100 | / | ||
Diameter | 1.5mm² | 1.5mm² | 2.5mm² | 2.5mm² | 2.5mm² | / | ||
type | C10 | C13 | C16 | C20 | C25 | C32 | ||
Number | 70 | 90 | 110 | 140 | 170 | 220 | ||
Diameter | 1.5mm² | 1.5mm² | 1.5mm² | 1.5mm² | 2.5mm² | 2.5mm² | ||
Output | Load type | LED | ||||||
Ripple requirement (Flickering or flickering-Free) | Flicker value: less than 2% for whole dimming range | |||||||
Start up time | <1s (@230Vac) | |||||||
No-load output voltage | 55VDC Max. | |||||||
Operating mode | 150mA | 200mA | 250mA | 300mA | 350mA | 700mA | ||
Load output voltage range | 3-40V | 3-40V | 3-40V | 3-33V | 3-29V | 3-14V | ||
Full load output power | 0.45-6W | 0.6-8W | 0.7-10W | 0.9-10W | 1.05-10W | 2-10W | ||
Load output current | Single Current | |||||||
Output current/voltage tolerance | ±5% | |||||||
Wiring method | wirecross section:0.5mm² | |||||||
Control Method | Primary PUSH Dimming | Primary PUSH dimming (Max.lead length:20M) | ||||||
1-10V Dimming | NO | |||||||
Dimming Range | Primary PUSH & DALI dimming: 0%-100% | |||||||
Potentiometer | NO | |||||||
DALI Dimming | DALI dimming (Max.lead length:300M) | |||||||
Exception Protection Requirements | Output over temperature protection | Yes, without self recovery function(Can be inquired) | ||||||
Output short circuit protection | Yes, without self recovery function(Can be inquired) | |||||||
Operating Environment | Operating temperature/ humidity | -25℃~50℃ Humidity:85% (Non-condensing) | ||||||
Storage temperature/ humidity | -40℃~80℃, Humidity:10%–95% | |||||||
Max. case temp(Tc) | 85℃ | |||||||
Safety & EMC | EMC standard | EN55015 EN61547 EN61000-3-2 EN61000-3-3 | ||||||
DALI protocol standard | IEC62386-102 IEC62386-207 DT6 251 253 | |||||||
Safety standard | EN61347-1 EN61347-2-13 | |||||||
Certification | CE | |||||||
Withstand voltage | 3750Vac, 5mA, 60s (Input “L N”- Output “SEC”) | |||||||
Others | Degrees of protection | IP20 | ||||||
Type of protection | Class II | |||||||
Installation type | Independent installation | |||||||
Installation dimension | 64.5*40*23mm | |||||||
Blackout memory function | Yes, PUSH blackout memory | |||||||
PUSH dimming synchronization | 15 units Max. | |||||||
Packaging requirement | white box+ Instructions Clapboard Outer Carton(K=A) | |||||||
Weight | 80g | |||||||
Life | 5 years guarantee @Ta full load | |||||||
Note: All parameters are tested at the input voltage of 230Vac and 25 degree environment unless specified. |
ON/OFF & Description of Dimming Operation
N/A