HomeProducts

MC002D 6

5.8GHz DC microwave motion sensor

Get a Quote

Features

  • Built in motion sensor and daylight sensor
  • Powered by low voltage 7.5-12VDC, output ON/OFF and PWM signal
  • Slim design makes is suitable for more luminaries
  • Sensor parameter can be optional via DIP switch
  • 5 years warranty

Size and Function Diagram

Parameter characteristics

Input DC Input Voltage 7.5-12V DC
Input Current <15mA
Voltage Ripple <100mVp-p
Output Working Mode 5V High and low frequency signal(output high level when PWM is 0V) 5V PWM signal
Sensor parameters Operating Frequency 5.8 GHz ±75 MHz
Transmitting power 1mW Max.
Hold time 5S/90S/3min/10min
Stand-by DIM Level 20%(different driver, different brightness)
Stand-by period 0s/30S/10min/+∞(PWM signal)
Detection Area 100%/75%/50%25%
Daylight Sensor 5lux/15Lux/50Lux/Disable(ambient light diffusion)
Detecting Radius
(Detection Area 100%)
Ceiling mounting(mounting height 3m): 0.3m/S ≥4m, 1m/S ≥2.5m ; Wall Mounting(mounting height: 2m): 0.3m/S ≥6m,1m/S ≥3m
Mounting Height Typical value: 3m (6m Max )
Detecting Angle 150°
Operating Environment Operating Temperature ’-25~70℃
Storage Temperature Temperature: -40℃…+80℃Humidity: 85%(non-condensing)
Certification Standards Certified CE RED
Environmental requirements Compliant to RoHS
Other Wiring Method terminal 4pin 2.54mm terminal
wires AWG24, Exposed wire diameter: 285mm, 4pin terminal block
IP Rating IP20
Installation Built-in installation
Package Clapboard+carton(K=A)
Net Weight 18g without cable
Lifetime 5 years warranty@Ta
Note:
1. “N/A” means not available.
2. Detection area is effected on volume of motion object and motion speed. The detection area is tested by a 165cm height person and walking speed is 0.3m/s.

Product details

Initialization
Sensor turns on the light at 100% brightness when first power on, and turns off the light after ten seconds. During the initialization, sensor does not detect moving signals.

 

Factory Setting
Detection Area: 100%, Hold Time:5S ,Stand-by period:0S , Stand-by dim level:20%, Daylight sensor: Disable

 

Application Notice

  • The sensor should be installed by a professional electrician. Please turn off the power before installing, wiring, changing the setting of the DIP switch.
  • Microwaves cannot penetrate metal. Do not place the product in a closed metal lamp or a half-closed metal lamp and metal or glass are not allowed to cover above the product. If antenna needs to pass through the metal plate, please ensure that the top of the sensor is close to the metal plate.
  • The distance between any inductive sensors should be greater than two meters. Keep sensor away from switches, routers and other wireless devices to avoid radio interference, more than three meters. The antenna surface of the microwave module should not be directly facing input AC and output DC to avoid low or high frequency signals affecting the normal operation of microwave sensor’s antenna.
  • Vibration signals will be regarded as moving signals to trigger the sensor. Avoid using objects that vibrate for a long time around the sensor, such as large metal equipment, pipes, air conditioning outlets, exhaust vents, smoke exhaust machine ports, shaking fans, etc. Pets in detecting area may trigger sensing.
  • This model is suitable for ceiling mounting. If wall mounting, the detecting area will enlarge, which makes microwave penetrate wall or light not turn off. Please change “detection area” to 25%. If 25% is useless, please avoid wall mounting or contact the manufacturer for technical support.
  • This model is suitable for ceiling mounting. If wall mounting, the detecting area will enlarge which makes microwave penetrate wall or light not turn off, and please change sensitivity to 25%. If 25%sensitivity is useless, please avoid wall mounting or contact the manufacturer for technical support.(7) Due to continuous improvement, the contents of this instruction could be changed without prior notice.
  • Different PWM drivers, different low brightness. The daylight threshold is measured in a sunny environment without shadow and ambient light diffuse reflection.
  • Ambient lux level could be different in different environment, weather, climate, time-of-day and season.
  • Sensitivity distance is related to moving speed of objects, size of moving objects, mounting height, mounting angle, working environment, reflecting materials and others.
  • Given detecting distance is typical value that was measured by 165cm high testers in an indoor open environment.
  • This product needs using with voltage-stabilized DC power supply whose input voltage is stable and ripple factor is low(ripple factor is lower than 100mV; load current is greater than 25mA).

Wiring suggestions

Installation suggestion

*The sensor is designed to connect one load only. Connect more than one load may damage the sensor.