HomeProducts

MC083S RC

High installation sensor

Get a Quote

Features

  • High installation, can support 12m mounting
  • users can configure each sense parameter according to needs.
  • Support high-sensitivity and low-sensitivity mode (for metal ceiling, metal reflective surface installation environment)
  • Override function
  • 5 years warranty

Size and Function Diagram

Parameter characteristics

Input Operating Voltage 108-305V AC 50/60Hz
Rated Voltage 120/277V AC 50/60Hz
Stand-by Power ≤1W
Surge Test L–N: 1kV
Output Working Mode ON/OFF function
Type of  Load Inductive or resistive Load
Load Capacity 2A @120Vac ,3A@277Vac, 3A@220-240Vac
Max. Surge Capacity 30A (50%Ipeak,twidth =500uS, 230Vac full load, cold start);
60A (50% Ipeak, twidth=200uS, 230Vac, full load, cold start)
Sensor Parameters Operating Frequency 5.8 GHz ±75 MHz, ISM Band.
Transmitting power 0.5mW Max.
Hold time 5S/30S/1min/3min/20min/30min
Detection Area 100%/75%/50%/10%
Daylight Sensor 5Lux/15Lux/30Lux/50Lux/100Lux/150Lux/Disable(Ambient light diffusion)
Detecting Radius See detection pattern
Mounting Height 12m Max
Detecting Angle 150°
Operating Environment Operating Temperature -25℃…+60℃
Storage Temperature Temperature:-40℃…+80℃;
Humidity:10%-95% (non-condensing)
Certificate Standards Safety standards EN61058-1, UL60703-1
EMC standards EN300440; EN301489-1; EN55015; EN61547; EN61000-3-2; EN61000-3-3; EN62479
Environmental Requirement Compliant to RoHS
Certificate Standards Certificate CE, RED,UL,FCC
Others Input/output terminal specifications Push-type terminal block; wire diameter: 0.75-1.5mm²
IP Rating IP20
Protection Class Class II
Installation Built-in installation
Dimension 93.5*45*28.5mm
Package Bubble bag + partition + outer box (K=A)
Net Weight 61.2g
Lifetime 5 years warranty @Ta 230V full load
Note
1. “N/A”means not available.
2. Detection area is effected on volume of motion object and motion speed. The detection area is tested by a 165cm height person and walking speed is 0.5m/s.

Product details

Initialization

On/Off function

After power on, the sensor automatically turns on light at 100% brightness. After 10sec, it turns off the light. During the initialization, the sensor is not able to detect movement.

 

Factory Setting

Detection area: 100%, Hold Time: 5S, Daylight sensor: Disable, Detection mode: HS

 

Override Sensor

Power off, quick switch ON/OFF sensor 3 times (ON-OFF-ON-OFF-ON) within 2sec to override sensor function. Lights will blink 3 times and then switch ON all the time. Power off and on again to recover sensor function.

 

Application Notice

1)The product can work with any kinds of control grear..

2) The sensor should be installed by a professional electrician. Please turn off the power before installing, wiring, changing the setting of the DIP switch.

3) The sensor mounted in a plastic, glass lampshade would reduce the sensitivity of the sensor. For every 3 mm increase in thickness, the sensitivity would reduce by 20%.

4) The sensing distance will be affected by the height of the sensor installation, the size of the object being detected, and the speed of movement.

5) Daylight the value is in a sunny environment with no shadows and ambient light diffuse reflection conditions. The values illumination detected by sensor may vary in different environment, at different times, in different seasons, and in different climates.

6) The parameters of the sensor may need to be reconfigured in different installation environments. Please refer to the following instructions or contact the manufacturer.

7) This sensor is for indoor use only. Outdoor use will affect the waterproof effect, wind and moving objects around would cause false triggering.

8) The distance between any inductive sensors should be greater than 3m.

9) When the sensor is installed in a metal illuminance , a metal reflective surface, or a narrow enclosed environment, the microwave will be reflected repeatedly and cause false triggering. Please reduce the sensitivity or contact the manufacturer for technical support.

10) Do not place the sensor close to high-density objects such as metal, glass, mixed-use walls, etc. The sensor may be triggered by mistake.

11) Please ensure that there are no moving signals around the sensor, such as fan, DC motor, sewer, air outlet, etc., the sensor may generate false triggers.

Wiring suggestions

 

*The sensor is designed to connect one load only.

Connect more than one load may damage the sensor.

Installation suggestion

N/A