Input | Rated Voltage | 220-240VAC 50/60Hz |
Stand-by Power | ≤0.15W | |
Surge Test | 1KV(L/N,EN61000-4-5) | |
Output | Output Signal | ON/OFF |
Load Capacity | 400W@230VAC(Inductive Load),800W @230VAC(Resistive Load) | |
Load Surge Current | 60A(50% Ipeak, twidth 200us @230Vac full load, cold start) | |
Sensor Parameters | Operating Frequency | 5.8 GHz ±75MHz,ISM wave band |
Transmitting power | 1mW Max. | |
Detection Range(Radius) | Ceiling Mounting at 3m high:0.3m/s ≥3.5m,1m/s ≥2.5m ; Wall Mounting at 2m high:0.3m/s ≥8m,1m/s ≥4m Test condition: 100% sensitivity, 60 ㎡no visible obstruction indoors |
|
Mounting Height | 3m (5m Max ) | |
3db Beam Angle | 90°@XZ | |
95°@YZ | ||
Operating Environment | Operating Temperature | Built-in installation: 20T60 |
Storage Temperature | -40℃…80℃, Humidity≤85%(Non-condensing) | |
Certificate Standards | Certificates | CE、RED、UKCA、SAA、CB、TUV |
Environmental Requirement | Compliant to RoHS 2.0, Reach | |
Safety (LVD) standard | EN61058-1-2 | |
EMC Standards | EN61000-3-2,EN61000-3-3,EN62479, EN301489-1, EN55015, EN300440 | |
IP Rating | IP20 | |
Product classification | Class II | |
Others | Wiring | Press-in Type Terminals, wire diameter: 0.5-1.0mm2 |
Installation | Built-in | |
Package | bubble pack + cardboard + outer carton(K=A) | |
Net Weight | 38±5g | |
Lifetime | 5 years warranty @Ta 230V full load |
Initialization
After power on, the sensor automatically turns on light to 100% brightness and turns off light in 10 seconds. During initialization, sensor is not able to detect movement.
Factory Setting
Sensitivity:100%, Hold-time:5s, Daylight threshold:Disable
Application Notice
*The sensor is designed for connect one load only.
Connect more than one loads may damage the sensor.
*When installing, please pay attention to the distance between the microwave antenna and the metal frame.