Input | Operating Voltage Rage | 108-305VAC 50/60Hz |
Rated Voltage | 120-277VAC 50/60Hz | |
Stand-by Power | <1W | |
Surge Test | L N: 1kV | |
Output | Working Mode | On-off |
Type of Load | Resistive & inductive | |
Load Capacity | 400w – inductive or 800w – resistive | |
Max. Surge Capacity | 30A(Measured at 50% Ipeak,twidth=500us @230Vac Cold start)or 60A(Measured at 50% Ipeak,twidth=200us @230Vac Cold start) | |
Sensor Parameters | Operating Frequency | 5.8 GHz ±75 MHz,ISM band |
Transmitting power | 0.5mW Max. | |
Hold time | 5s/30s/1min/3min/5min/10min/20min/30min | |
Detection Area) | 25%/50%/75%/100% | |
Daylight Sensor | Daylight threshold:5lux/15lux/30lux/50lux/100lux/150lux/Disable(no shadow or direct light to sensor) | |
Detecting Range | See detection pattern | |
Mounting Height | 15m Max. | |
Detection Angle | 150°(wall mount), 360°(ceiling mount) | |
Operating Environment | Operating Temperature | -35℃…+55℃ |
Storage Temperature | -40℃…+80℃ humidity:10%-95% (non-condensing) | |
Certificate Standards | Safety standards | IEC60669-2-1, IEC60669-1 AS/NZS 60669.1, AS/NZS 60669.2.1 UL60730-1 |
EMC standards | EN55015, EN61000-3-2, EN61000-3-3, EN61547 AS/NZS CISPR 15, AS/NZS 4268 FCC Part 15C, Part 15B EN 60950-1, EN301489-1, EN 201489-3, EN300440 |
|
Environment Request | Compliant to RoHS | |
Certificate | CE | |
Others | Wiring | UL1015,2*18AWG,exposed line length 810mm |
Wiring color | L(Black), N(White), L’(Red) | |
IP Rating | IP65 | |
Protection Class | Class II | |
Installation | M20 side mount | |
Dimension | See dimension | |
Package | White paper box+cartons | |
Net Weight | 80g | |
Lifetime | 5 years warranty@Ta 230V full load | |
Note: 1. Detection area is effected on volume of motion object and motion speed. The detection area is tested by a 165cm height person and walking speed is 0.5m/s. |
Initialization
On/Off function: After power on, the sensor automatically turns on light at 100% brightness. After 10sec, it turns off the light. During the initialization, the sensor is not able to detect movement.
Factory setting
Detection area:75%, Hold time:5s , Daylight Sensor: Disable
Application Notice
*The sensor is designed to connect one load only.
Connect more than one load may damage the sensor.
N/A