                | Input | Rated Voltage | 120/277/347VAC 50/60Hz | |||||
| Stand-by Power | ≤1W | ||||||
| Surge Test | 1KV(L/N, EN61000-4-5) | ||||||
| Output | Output dimming Mode | 0-10VDC Dimming Signal | ON/OFF Signal | ||||
| Load Capacity | @120VAC 3.6A Ballast      @277VAC 3.4A Ballast @347VAC 3.3A Ballast | ||||||
| Max. Surge Capacity | 50A (50% Ipeak, twidth =500us, 230Vac full load, cold start) | ||||||
| Dim interface | 0-10V Dimming | < 50mA(Non-constant source) 10%(0.5-1V) 20%(1.9-2.1V) 30%(2.9-3.1V) 40% (3.9-4.1V) | |||||
| Sensor Parameter | Operating Frequency | 5.8 GHz ±75MHz, ISM wave band. | |||||
| Transmitting power | 1mW Max. | ||||||
| Detecting Radius | 1m/s ≥2.5m. @ 3m ceiling mounting, 1m/s ≥4m @ 2m wall mounting Test conditions : the product is set to 100% sensitivity, and there is no obvious occlusion in the room of 60㎡, 165cm person. | ||||||
| Mounting Height | 3-6m (ceiling mounting) | ||||||
| 3db beam angle | 80°@XZ plane | ||||||
| 96°@YZ plane | |||||||
| Environment | Operating Temperature | -35~70℃ | |||||
| Storage Temperature | -40℃~80℃, Humidity: ≤85%(Non-condensing) | ||||||
| Certificate Standard | Certificate | UL, CE, RED | |||||
| Environmental?Requirement | Compliant to RoHS 2.0, Reach | ||||||
| Safety Standards | UL60730 | ||||||
| IP Rating | IP20 | ||||||
| Protection Class | Class II | ||||||
| Other | Wiring | Press-in terminals wire diameter: L /N /L’: 18AWG +/-Dimming port: 22AWG | |||||
| Installation | Built-in | ||||||
| Package | Clapboard + Carton(K=A) | ||||||
| Net Weight | 120±5g | ||||||
| Lifetime | 5 years warranty @Ta 230V | ||||||
Initialization
Default setting
Sensitivity: 100%, Hold time: 8s, Daylight sensor: Disable, Stand by period: 0s, Stand by DIM level: 10%
Application Notice


Note:
The sensor is allowed to be connected to one load only. The sensor may be damaged if connecting more than one load.
Sensor antenna should be above LED tray.
 
                    