HomeProducts

MC087D 3

DC Controller(Microwave)

Get a Quote

Features

  • 12V DC input, 0-10V dimming signal or PWM dimming signal output, suitable for DC systems or LED driver with 12V DC auxiliary power output.
  • Three-step and two-step dimming is optional, detection area is adjustable.
  • Patented antithetical dipoles antenna design and Adaptive Algorithm, which effectively solves the problem of low installation height of columnar antenna sensors and false triggering caused by side-lobe radiation of the antenna when installed in a metal room.
  • Widely used in parking lots and Logistics warehouse and other complex environment places.
  • Sensor parameters can be set by remote control and DlP switches, easy to configured.

Dimension & Function Diagram

Parameter characteristics

Input Rated Voltage 12+1Vdc
Working Current 26±3mA
Ripple Voltage <100mVp-p
Output Output signal PWM dimming signal;  0-10V DC dimming signal
Daylight Sensor Daylight Sensor Daylight Threshold——
DIP: 5Lux/15Lux/50lux/Disable
Remote: 5Lux/15Lux/30Lux/50lux/100Lux/150Lux/Disable
Stand-by DlM Level 10%/20%/30%/50%
Sensor Parameters Working Frequency 5.8GHz+75MHz, ISM band
Transmitting Power 1mW Max.
Detection Area 100%/75%/50%/25%
Hold Time DIP: 5S/1min/3min/10min
Remote: 5S/30S/1min/3min/5min/10min/20min/30min
Stand-by Period DlP: 0S/1min/3min/+∞
Remote: 0S/10S/1min/3min/5min/10min/30min/+∞
Detection Area(Radius) Ceiling mounting 3m: r≥4m@0.3m/s, r≥2.5m@1m/s;
Wall mounting: r≥5m@0.3m/s, r≥3m@1m/s
Test condition: Set 100% sensitivity, open 60 m² indoor area.
Mounting Height 3m (6m Max)
Environment Working Environment Temperature -25~60℃
Storage Temperature -40~80℃   Humidity: ≤85% non-condensing
Certificate Standards Certified CE
Environmental Requirements RoHS 2.0, Reach
IP Rating IP20
Other Wiring 3pin 2.0mm terminal
Installation Built-in
Package Clapboard+Carton(K=A)
Net Weight Pending
Lifetime 5 years warranty@Ta

Product details

Initialization

The light will be turned on 100% brightness after power on, and will be turned off after 10 seconds. During initialization, no external motion sensing signal will be detected.

 

Default Setting

Sensitivity: 100%, Hold time:5s, Daylight sensor: Disable, Stand-by period: 0s, Stand-by dim level: 20%

 

Application Notice

  • The sensor should be installed by a professional electrician. Please turn off the power before installing, wiring, changing the setting of the DIP switch.
  • Sensitivity area is related to moving speed of objects, size of moving objects, mounting height, mounting angle, working environment, reflecting materials and etc.. Given detecting area is typical value that was measured by 165cm/65kg testers in an indoor open environment.
  • The detection area of the microwave sensor when installed on the wall will be greatly increased compared to when installed on the ceiling. If adopts wall ceiling, please reduce the sensitivity or contact our company to confirm the usage settings. The daylight thresholds are measured on a sunny day without shadow and in an ambient light diffuse reflection status. Different environment and climate cause different brightness values that daylight sensor measures.
  • Sensor parameters may need to be reconfigured in different installation environments, please refer to the following instructions or contact the manufacturer.
  • Sensor is for indoor use only. The waterproof effect for outdoor or half-outdoor use will be affected. Wind, rain, and moving objects may cause false triggering.
  • The installation height of the sensor product cannot exceed 6 meters, and the optimal height is 3 meters. The distance between the two sensors should be greater than 3m.
  • When the sensor is installed in a metal lamp, on a metal reflective surface, or in a small closed environment, the microwave will be reflected multiple times and cause false triggering. Please reduce the sensitivity of the sensor or contact the manufacturer for technical support.
  • Please make sure that there are no moving signals such as fans, DC motors, sewer pipes, air outlets, etc. around the sensor, otherwise the sensor may cause false triggering.
  • Microwaves cannot penetrate metal. Do not place product in a closed or a half-closed metal lamp. Neither metal nor glass is not allowed to cover above the product.
  • Sensor are equipped with different PWM drivers, and the low-brightness effect may be different.
  • DC regulated power supply with stable output voltage and low ripple coefficient must be used. The ripple of the power supply should be less than 100mV ; the load current should be greater than 30mA

Wiring suggestions

Installation suggestion