HomeProducts

MC083V 99

AC sensor(microwave)

Get a Quote

Features

  • Patented microwave antenna, mounting height is 15m Max, suitable to install in most of warehouses
  • Work with 1-10V dimmable LED driver, easy to achieve 2-step or 3-step dimming function
  • Supports high-sensitivity and low-sensitivity modes (for metal ceilings, metal reflector mounting environments)
  • Sensor data can be set by DIP switch & remote control.
  • 5 years warranty
  • UL listed certificate

Size and Function Diagram

Parameter characteristics

Input Rated Voltage 120/277V AC 50/60Hz(US);220-240VAC 50/60Hz(Europe)
Stand-by Power ≤0.5W
Surge Test 1kV(L/N,EN61000-4-5)
Output Output Control ON-OFF 0-10VDC Dimming Signal
Load Capacity 4A @120Vac 3A @277Vac
Max. Surge Capacity 50A (50% Ipeak, twidth =200us, 230Vac full load, cold start);
0-10VDimming < 50mA (Non-constant current source)
10%(1.4-1.6V) 20%(1.9-2.1V) 30%(2.9-3.1V) 50% (4.9-5.1V)
Sensor Parameter Operating Frequency 5.8 GHz ±75MHz, ISM wave band.
Transmitting power 3mW Max.
Hold time 5S/30S/1min/3min/20min/30min/60min(setting by DIP)
5s/30s/1min/3min/5min/10min/20min/30min (setting by remote)
Stand-by dim Level 20%(1.9-2.1V)/30%(2.9-3.1V)(setting by DIP)
10%(1.4-1.6V)/20%(1.9-2.1V)/30% (2.9-3.1V )/50%(4.9-5.1V)(setting by remote)
5s/30s/1min/3min/5min/10min/20min/30min (setting by remote)
Stand-by Period 0S/5S/5min/10min/30min/60min/+∞(setting by DIP)
0s/10s/1min/3min/5min/10min/30min/+∞ (setting by remote)
Detection 100%/75%/50%/25%(setting by DIP)
100%/75%/50%/25% (setting by remote)
Daylight Sensor Daylight threshold 5lux/15lux/30lux/50lux/100lux/150lux/Disable
5lux/15lux/30lux/50lux/100lux/150lux/Disable ( setting by remote)
Daylight  priority ON Off
5lux/15lux/30lux/50lux Turn on Value+(50-150Lux)
100lux Turn on Value+(50-150Lux)
150lux Turn on Value+(50-150Lux)
Detecting Radius ceiling mounting12m r≥3m@1m/s, 39.4ft r≥10ft@3.28ft/s Testing condition: 100% sensitivity, open 60 ㎡ indoor area.
Mounting Height 12m(15m Max )(39.4ft Max 49.2ft)
Environment Operating Temperature -25~60°C(-13~140°F)
Storage Temperature -40℃~80℃(-40~176°F), Humidity: ≤85%(Non-condensing)
Certificate Standard Certificate UL(pending) CE
Environmental Requirement Compliant to RoHS 2.0, Reach
Safety standards EN61058-1,UL60703-1
EMC standards EN300440; EN301489-1; EN55015; EN61547; EN61000-3-2; EN61000-3-3; EN62479
IP Rating IP20
Product Class Class Ⅱ
Other Wiring AC wire:(L:Black;N:White;L’:Red) 1-10V:(GND:Pink;10V:Purple)
Installation Built-in
Package Bubble bag + Clapboard + Carton(K=A)
Net Weight 129.4±5g
Lifetime 5 years warranty @Ta

Product details

Initialization

After power on, the sensor automatically turns on light to 100% brightness and turns off light in 10seconds. During initialization, sensor is not able to detect movement.

 

Default setting

Sensitivity: 100%, Hold time: 5s, Daylight sensor: Disable, Stand-by Period: 0s, Stand-by DIM Level:20%

 

Application Notice

  • The sensor should be installed by a professional electrician. Please turn off the power before installing, wiring, changing the setting of the DIP switch.
  • Sensitivity area is related to moving speed of objects, size of moving objects, mounting height, mounting angle, working environment, reflecting materials and etc.. Given detecting area is typical value that was measured by 165cm/65kg testers in an indoor open environment.
  • The detection area of the microwave sensor when installed on the wall will be greatly increased compared to when installed on the ceiling. If adopts wall ceiling, please reduce the sensitivity or contact our company to confirm the usage settings. The daylight thresholds are measured on a sunny day without shadow and in an ambient light diffuse reflection status. Different environment and climate cause different brightness values that daylight sensor measures.
  • Sensor parameters may need to be reconfigured in different installation environments, please refer to the following instructions or contact the manufacturer.
  • Sensor is for indoor use only. The waterproof effect for outdoor or half-outdoor use will be affected. Wind, rain, and moving objects may cause false triggering.
  • The installation height of the sensor product cannot exceed 15 meters, and the optimal height is 12 meters. The distance between the two sensors should be greater than 3m.
  • When the sensor is installed in a metal lamp, on a metal reflective surface, or in a small closed environment, the microwave will be reflected multiple times and cause false triggering. Please reduce the sensitivity of the sensor or contact the manufacturer for technical support.
  • Please make sure that there are no moving signals such as fans, DC motors, sewer pipes, air outlets, etc. around the sensor, otherwise the sensor may cause false triggering.
  • Microwaves cannot penetrate metal. Do not place product in a closed or a half-closed metal lamp. Neither metal nor glass is not allowed to cover above the product.
  • For the new installation environment, it is recommended to test 5pcs samples before installation.

Wiring suggestions

*The sensor is designed for connect one load only. Connect more than one loads may damage the sensor.

Installation suggestion

N/A